TFR-8 3x 150mm²

Description

Description

Standards

  • Product
    Nexans specification
  • National
    KS C IEC 60502-1

Application

Power cable for residential, commercial building and distribution circuit.
The flame retardant cable for tray conformed to the standard of technique of electrical equipment.

Construction

1. Conductor: Annealed copper stranded conductor, Class 2

2. Fire resistant Mica tape.

3. Insulation: Cross-linked polyethylene (XLPE), Max operating temperature: 90°C.

4. Unit: Cabling circularly insulated solid wire in case of more 2 cores

5. Outer sheath: Black flame retardant PVC (TFR-PVC)

 

Colors

1 core: Natural color
2 cores: White, Black
3 cores: White, Black, Red
4 cores: White, Back, Red, Green

 

Certification

KETI (Safety certification for electrical products)

TFR-8 0.6/1kV design

##image:56140##

Conductor 

Mica tape 

Insulation 

Filler 

Binder tape 

Outer sheath (TFR PVC)

 

The values of insulation resistance is not defined but only constant number of insulation resistance is defined.
(K=min. 36.7MΩ.km at 90℃)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Annealed copper
Type of conductor
Stranded, class 2
Construction type
Circular compacted strand
Insulation
Micatape + XLPE
Outer sheath
PVC
Colour
White / Black / Red
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
150 mm²
Conductor diameter
14.4 mm
Average insulation thickness
1.4 mm
Average sheath thickness
2.3 mm
Outer Diameter
50.5 mm
Approximate weight
4790 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.124 Ohm/km
Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 60 °C
Flame retardant
KSC IEC 60332-3
Bending factor when installed
12 (xD)

Resources

Resources

Current capacity table XLPE insulation multicore single phase

XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Conductor cross-section
150.0
318.0
253.0
290.0
230.0
334.0
261.0
441.0
mm²
324.0
Cu
306.0
Al
238.0
Cu
343.0
Al
261.0
Cu
473.0
Al
346.0
A1 Insulated conductors in conduit in a thermally insulated wall
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Multi-core cable in ducts in the ground
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table XLPE insulation multicore three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Conductor cross-section
150.0
285.0
226.0
259.0
206.0
300.0
240.0
371.0
mm²
283.0
Cu
251.0
Al
197.0
Cu
287.0
Al
220.0
Cu
399.0
Al
304.0
A1 Insulated conductors in conduit in a thermally insulated wall
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Multi-core cable in ducts in the ground
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table XLPE insulation single core single phase

XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Conductor cross-section
150.0
318.0
253.0
393.0
307.0
441.0
324.0
mm²
306.0
Cu
238.0
Al
343.0
Cu
261.0
Al
504.0
Cu
389.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single core or Multi-core cable in ducts in the ground
D2 Single core or Multi-core cables designed to be buried directly in the ground
F Single-core flat cables, touching in free air

Current capacity table XLPE insulation single core three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Conductor cross-section
150.0
285.0
226.0
342.0
267.0
371.0
283.0
251.0
mm²
197.0
Cu
287.0
Al
197.0
Cu
464.0
Al
358.0
Cu
444.0
Al
343.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single core or Multi-core cable in ducts in the ground
D2 Single core or Multi-core cables designed to be buried directly in the ground
F Single-core flat cables, touching in free air
Ft Single-core trefoil cables, touching in free air

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close