TFR-CVV 10x10mm²
Description
Description
Standards
-
NationalKS C IEC 60502-1; KWS 411
Application
Power cable for residential, commercial building and distribution circuit.
The flame retardant cable for tray conformed to the standard of technique of electrical equipment.
Construction
1. Conductor: Stranded annealed round plain copper, Class 2
2. Insulation: PVC, operating temperature 70°C.
3. Unit: Cabling circularly insulated solid wire in case of more than 2 cores
4. Outer sheath: Black flame retardant black PVC (TFR PVC)
Colors
2 cores: White /Black
3 cores: White / Black /Red,
4 cores: White / Black / Red / Green
More 5 cores: Numbering on black or red core. The others are white
Certification
KETI
KWS (Collective standard)
TFR-CVV 0.6/1kV design
| ##image:55999## |
Insulation Filler Binder tape Outer sheath (TPR PVC)
|
The values of insulation resistance is not defined but only constant number of insulation resistance is defined
(K=min. 36.7MΩ.km at room temperature, min. 0.037MΩ.km at 70℃)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Fire safety characteristics
Fire safety characteristics
Resources
Resources
Current capacity table PVC insulation multicore single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground| Conductor cross-section |
|
|
|
|
|
|
|
|||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 10.0 | 46.0 | 36.0 | 43.0 | 33.0 | 52.0 | 41.0 | 63.0 | 49.0 | 60.0 | 47.0 | 64.0 | 0.0 | 70.0 | 54.0 |
| A1 Insulated conductors in conduit in a thermally insulated wall |
| A2 Multi-core cable in conduit in a thermally insulated wall |
| B2 Multi-core cable in conduit on a wooden wall |
| C Single-core or multi-core cable on a wooden wall |
| D1 Multi-core cable in ducts in the ground |
| D2 Multi-core cables designed to be buried directly in the ground |
| E Multi-core cable in free air |
Current capacity table PVC insulation multicore three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground| Conductor cross-section |
|
|
|
|
|
|
|
|||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 10.0 | 42.0 | 32.0 | 39.0 | 31.0 | 46.0 | 36.0 | 57.0 | 44.0 | 50.0 | 39.0 | 54.0 | 0.0 | 60.0 | 46.0 |
| A1 Insulated conductors in conduit in a thermally insulated wall |
| A2 Multi-core cable in conduit in a thermally insulated wall |
| B2 Multi-core cable in conduit on a wooden wall |
| C Single-core or multi-core cable on a wooden wall |
| D1 Multi-core cable in ducts in the ground |
| D2 Multi-core cables designed to be buried directly in the ground |
| E Multi-core cable in free air |
Current capacity table PVC insulation single core single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground| Conductor cross-section |
|
|
|
|
|
|
||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 10.0 | 46.0 | 36.0 | 57.0 | 44.0 | 63.0 | 49.0 | 60.0 | 47.0 | 64.0 | 0.0 | 0.0 | 0.0 |
| A1 Insulated conductors in conduit in a thermally insulated wall |
| B1 Insulated conductors in conduit on a wooden wall |
| C Single-core or multi-core cable on a wooden wall |
| D1 Single core or Multi-core cable in ducts in the ground |
| D2 Single core or Multi-core cables designed to be buried directly in the ground |
| F Single-core flat cables, touching in free air |
Current capacity table PVC insulation single core three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground| Conductor cross-section |
|
|
|
|
|
|
|
|||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 10.0 | 42.0 | 32.0 | 50.0 | 39.0 | 57.0 | 44.0 | 50.0 | 39.0 | 54.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| A1 Insulated conductors in conduit in a thermally insulated wall |
| B1 Insulated conductors in conduit on a wooden wall |
| C Single-core or multi-core cable on a wooden wall |
| D1 Single core or Multi-core cable in ducts in the ground |
| D2 Single core or Multi-core cables designed to be buried directly in the ground |
| F Single-core flat cables, touching in free air |
| Ft Single-core trefoil cables, touching in free air |