TFR-CVV 15x1.5mm²
Description
Description
Standards
- 
                                            NationalKS C IEC 60502-1; KWS 411
 
Application
Power cable for residential, commercial building and distribution circuit.
The flame retardant cable for tray conformed to the standard of technique of electrical equipment.
Construction
1. Conductor: Stranded annealed round plain copper, Class 2
2. Insulation: PVC, operating temperature 70°C.
3. Unit: Cabling circularly insulated solid wire in case of more than 2 cores
4. Outer sheath: Black flame retardant black PVC (TFR PVC)
Colors
2 cores: White /Black
3 cores: White / Black /Red,
4 cores: White / Black / Red / Green
More 5 cores: Numbering on black or red core. The others are white
Certification
KETI
KWS (Collective standard)
TFR-CVV 0.6/1kV design
| ##image:55999## | 
             
 Insulation Filler Binder tape Outer sheath (TPR PVC) 
 
  | 
        
The values of insulation resistance is not defined but only constant number of insulation resistance is defined
(K=min. 36.7MΩ.km at room temperature, min. 0.037MΩ.km at 70℃)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Current capacity table PVC insulation multicore single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground| Conductor cross-section | 
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | 
| 1.5 | 14.5 | 0.0 | 14.0 | 0.0 | 16.5 | 0.0 | 19.5 | 0.0 | 22.0 | 0.0 | 22.0 | 0.0 | 22.0 | 0.0 | 
| A1 Insulated conductors in conduit in a thermally insulated wall | 
| A2 Multi-core cable in conduit in a thermally insulated wall | 
| B2 Multi-core cable in conduit on a wooden wall | 
| C Single-core or multi-core cable on a wooden wall | 
| D1 Multi-core cable in ducts in the ground | 
| D2 Multi-core cables designed to be buried directly in the ground | 
| E Multi-core cable in free air | 
Current capacity table PVC insulation multicore three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground| Conductor cross-section | 
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | 
| 1.5 | 13.5 | 0.0 | 13.0 | 0.0 | 15.0 | 0.0 | 17.5 | 0.0 | 18.0 | 0.0 | 19.0 | 0.0 | 18.5 | 0.0 | 
| A1 Insulated conductors in conduit in a thermally insulated wall | 
| A2 Multi-core cable in conduit in a thermally insulated wall | 
| B2 Multi-core cable in conduit on a wooden wall | 
| C Single-core or multi-core cable on a wooden wall | 
| D1 Multi-core cable in ducts in the ground | 
| D2 Multi-core cables designed to be buried directly in the ground | 
| E Multi-core cable in free air | 
Current capacity table PVC insulation single core single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground| Conductor cross-section | 
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | 
| 1.5 | 14.5 | 0.0 | 17.5 | 0.0 | 19.5 | 0.0 | 22.0 | 0.0 | 22.0 | 0.0 | 0.0 | 0.0 | 
| A1 Insulated conductors in conduit in a thermally insulated wall | 
| B1 Insulated conductors in conduit on a wooden wall | 
| C Single-core or multi-core cable on a wooden wall | 
| D1 Single core or Multi-core cable in ducts in the ground | 
| D2 Single core or Multi-core cables designed to be buried directly in the ground | 
| F Single-core flat cables, touching in free air | 
Current capacity table PVC insulation single core three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground| Conductor cross-section | 
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                	
                                                		 | 
                                                |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | 
| 1.5 | 13.5 | 0.0 | 15.5 | 0.0 | 17.5 | 0.0 | 18.0 | 0.0 | 19.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 
| A1 Insulated conductors in conduit in a thermally insulated wall | 
| B1 Insulated conductors in conduit on a wooden wall | 
| C Single-core or multi-core cable on a wooden wall | 
| D1 Single core or Multi-core cable in ducts in the ground | 
| D2 Single core or Multi-core cables designed to be buried directly in the ground | 
| F Single-core flat cables, touching in free air | 
| Ft Single-core trefoil cables, touching in free air | 
Our websites
Select your country to find our products and solutions
- 
                        Africa
                        
                        
                        
- Africa
 - Ghana
 - Ivory Coast
 - Morocco
 - North West Africa
 
 - Americas
 - Asia
 - Europe
 - Oceania